Ozone Layer Protection Act · Fluorocarbon Emissions Control Act · Designated Products

Japan Refrigerant Regulations

Understand Japan’s HFC phase-down, the Fluorocarbon Emissions Control Act, manufacturer/importer GWP target system for designated products, commercial-equipment inspection and leak-management duties, and the recovery requirements that shape HVAC/R compliance in 2026.

Last reviewed: August 2026 · Based primarily on current government and statutory sources
2026 Quick ViewLife-Cycle Regulation
60%2024–2028 Kigali levelJapan follows the developed-country Kigali HFC schedule: 60% of baseline for 2024–2028, then 30% from 2029.
750Household / office AC targetJapan’s designated-product system has used a 750 environmental-impact target for major household and store/office AC categories.
1,500Condensing-unit targetA 1,500 target applies to specified condensing units and stationary refrigeration units from the 2025 target year.
1,000 tCO₂Annual leak-report thresholdManagers whose calculated annual fluorocarbon leakage reaches at least 1,000 t-CO₂ must report under the national disclosure system.
Japan’s designated-product GWP values are manufacturer/importer weighted-average targets by product category—not a simple unit-by-unit legal ban. This distinction is essential when comparing Japan with EU or U.S. product restrictions.
Japanese Framework

Japan regulates fluorocarbons across their life cycle

The framework combines international HFC supply controls with manufacturer targets, equipment-owner inspection duties and recovery rules at service and disposal.

Supply

Ozone Layer Protection Act / Kigali

Japan implements Montreal Protocol controls on ozone-depleting substances and the Kigali HFC phase-down, including the 60% / 30% / 20% / 15% developed-country schedule.

Manufacturers & Importers

Designated Product Targets

The Fluorocarbon Emissions Control Act sets environmental-impact target values and target years for designated product categories, measured as a manufacturer/importer shipment-weighted average.

Equipment Owners

Inspections & Leak Management

Managers of Class I specified products—commercial AC and refrigeration using fluorocarbons—must conduct simple inspections and, for larger equipment, periodic expert inspections.

Service & Disposal

Filling, Recovery & Records

Registered filling/recovery businesses, equipment managers and disposal chains have duties for repair before refill, recovery, documentation and proper recycling/destruction.

Key principle: Japan’s GWP “target values” should not be written as if they were EU-style bans on every individual unit. They are designed to drive manufacturer/importer product portfolios toward lower environmental impact, while the equipment-management rules separately control leaks, inspections, filling and recovery.
Designated Product Targets

Selected Japanese refrigerant environmental-impact targets

The tables below summarize high-value HVAC/R target categories used under the Fluorocarbon Emissions Control Act. Some targets have already been reached; others are upcoming in refrigeration categories.

Read this table carefully: Target values are implemented as category-level goals for manufacturers/importers, typically based on shipment-weighted average environmental impact. Do not treat each value as a blanket “illegal above this GWP” statement for every unit.
Designated Product CategoryTarget ValueTarget YearHow to Read It
Household air conditioners — main covered category7502018Manufacturer/importer weighted-average environmental-impact target; R32 adoption supported this transition.
Store / office air conditioners — main covered category7502020Target applies by designated product category rather than as a universal per-unit ban.
Passenger-car air conditioners — covered passenger vehicles1502023Drove transition away from R134a toward much lower-GWP refrigerants such as R1234yf.
Condensing units / stationary refrigeration units — specified scope1,5002025Key current refrigeration target in the designated-product framework.
Commercial integral refrigerators1502029Current Japanese guidance adds a 150 target for specified commercial integral refrigeration equipment.
Central refrigeration — large new cold-storage scope1002019Very low target for defined very-large central refrigeration projects.
Central refrigeration — centrifugal compressor category1002029Current refrigeration guidance includes this later low-GWP target.
Central refrigeration — screw compressor category1502031Later target for specified central refrigeration equipment.
Japan uses a “top-runner style” transition mechanism.

Product manufacturers and importers are encouraged/required to achieve category targets over the defined target year framework, while actual equipment use also depends on safety, High Pressure Gas Safety Act considerations, product standards and lifecycle management rules.

New Products vs Equipment in Use

Japan separates refrigerant conversion from equipment-management duties

Manufacturers/importers face designated-product targets, while owners of commercial fluorocarbon equipment face inspection, leak, record and disposal obligations.

Manufacturers / Importers

Start with designated-product category and target year

For equipment placed on the Japanese market, identify whether it falls into a designated product category and how the manufacturer/importer target applies.

  • Identify the exact designated product category and target year.
  • Treat the published GWP / environmental-impact value as a manufacturer/importer portfolio target, not a simplistic per-unit ban.
  • Verify safety and product standards for A2L, A3, ammonia or CO₂ equipment.
  • Check whether future category revisions or new targets have been issued by METI / MOE.
  • For imports, confirm Japanese labeling, standards and product-law requirements beyond the fluorocarbon regime.
Class I Specified Products

Start with inspection, repair and refrigerant management

Commercial air-conditioning and refrigeration equipment using CFC/HCFC/HFC refrigerants is generally covered as Class I specified products.

  • Perform simple inspection at least once every three months for all Class I specified products.
  • For refrigeration equipment with compressor rated output ≥7.5 kW, conduct periodic inspection at least annually.
  • For AC ≥50 kW, periodic inspection at least annually; 7.5 to <50 kW AC at least once every three years.
  • When leakage is confirmed, identify and repair the source; repeated refilling without repair is generally prohibited.
  • Maintain inspection/service/filling/recovery records and follow recovery documentation at disposal.
What this means for R32 in Japan

R32 (GWP 675) helped manufacturers meet the 750 target used for major household and office AC categories and became widely adopted. But R32 is still an HFC controlled under the Kigali phase-down. Japan is therefore continuing to evaluate even lower-GWP and non-fluorocarbon pathways rather than treating R32 as the final endpoint.

Japan Transition Timeline

Key Japanese fluorocarbon milestones relevant in 2026

Japan’s transition combines Kigali supply reductions, designated-product target years and lifecycle-management obligations.

2015
Fluorocarbon Emissions Control Act frameworkThe revised law expands control from end-of-life recovery to the full fluorocarbon life cycle, including manufacturers, users and service/disposal chains.
2018
Household AC target750 target year for the main covered household air-conditioner category.
2020
Store / office AC target750 target year for the main covered store/office air-conditioner category.
Stronger disposal controls2020 amendments strengthen recovery confirmation and equipment-disposal controls.
2023
Passenger-car AC target150 target year for covered passenger-car air conditioners.
2024
Kigali 60% stepJapan enters the 2024–2028 developed-country HFC consumption/production control level at 60% of baseline.
2025
Condensing / stationary refrigeration target1,500 designated-product target year for the specified category.
2026
Leak-reporting system continuesManagers with calculated annual fluorocarbon leakage ≥1,000 t-CO₂ continue to report under the national disclosure system.
2029
Kigali 30% stepHFC control level falls to 30% of baseline for 2029–2033.
New refrigeration targetsSeveral commercial integral and central refrigeration categories enter 150 / 100 / 750 target years depending on equipment type.
2031
Central screw refrigeration targetSpecified screw-compressor central refrigeration category enters a 150 target year.
2036
Kigali endpointDeveloped-country HFC control level reaches 15% of baseline.
Common Refrigerants

How Japan’s framework affects five common refrigerants

Japan’s policy strongly connects refrigerant choice to product-category targets and lifecycle management rather than one universal national ban list.

R410AA1
GWP 2,090 classHigher-GWP legacy

Widely displaced in household and commercial AC by lower-GWP platforms such as R32 because the designated-product targets encourage lower portfolio GWP.

Explore R410A →
R32A2L
GWP 675Major Japan AC refrigerant

Below the 750 product target used in major AC categories, but still subject to Japan’s HFC phase-down as an HFC.

Explore R32 →
R1234yfA2L
Very low GWPAutomotive

Supports the 150 passenger-car AC target and has become an important R134a transition refrigerant.

Explore R1234yf →
R744A1
CO₂Natural refrigerant

A major Japanese “green refrigerant” pathway in commercial refrigeration, vending and cold-chain applications.

Explore R744 →
R717B2L
AmmoniaIndustrial

Important low-GWP industrial refrigerant, especially in larger refrigeration where toxicity and safety engineering can be managed.

Explore R717 →
Japanese target tables often use the government’s designated GWP values for policy calculations. Do not substitute another jurisdiction’s GWP table without checking the Japanese source.
Equipment Management & Leakage

Commercial fluorocarbon equipment has recurring inspection and record duties

Managers of Class I specified products have ongoing obligations during equipment use, not only at disposal.

3-Month Simple InspectionAll Class I specified products require simple inspection at least once every three months.
≥7.5 kW RefrigerationSpecified refrigeration/freezer equipment at or above 7.5 kW requires periodic inspection at least annually.
7.5–<50 kW ACSpecified air-conditioning equipment in this range requires periodic inspection at least once every three years.
≥1,000 t-CO₂ LeakageAnnual calculated leakage at or above this level triggers national leakage reporting.
Manager Obligations

Repair-before-refill and records are central to the Japanese model

The law aims to reduce emissions during the full equipment life cycle.

  • When a refrigerant leak is confirmed, the source should be identified and repaired; filling without repair is generally prohibited.
  • Managers must retain inspection, repair, filling and recovery records for covered equipment.
  • Registered Class I fluorocarbon filling/recovery operators handle refrigerant filling and recovery activities.
  • At disposal, fluorocarbon recovery and documentation are part of the controlled chain.
Compliance Workflow

Use Japan’s lifecycle framework instead of a one-number GWP shortcut

Separate manufacturer product targets from equipment-owner inspection and service obligations.

01Product Category
02Designated Product?
03Target Value / Year
04Fluorocarbon vs Natural
05Class I Equipment?
06Inspection Frequency
07Leak / Repair / Report
08Recovery / Disposal
09Final Project Decision
Japan’s target values are not EU-style bans. For compliance and content accuracy, explain whether a number is a manufacturer/importer weighted-average target, an equipment-owner inspection threshold, a leakage-reporting threshold or a Montreal/Kigali supply-control level.
Japan HVAC/R Project Support

Planning HVAC/R equipment for the Japanese market?

Use the Refrigerant Finder to identify low-GWP candidates, then verify the designated-product target, fluorocarbon lifecycle obligations, equipment safety and current METI / MOE requirements.