HFO/HFC/CO2 BlendA1Technical Profile

R480A RefrigerantRS-20 · A1 low-GWP R134a-class retrofit / transition blend

R480A is a nonflammable A1 refrigerant blend developed as a lower-GWP alternative for R134a-class applications. Published retrofit documentation for RS-20 identifies the composition as 5% CO₂, 86% HFO-1234ze and 9% HFC-227ea. Its combination of GWP 291 and A1 classification makes it especially interesting for retrofit discussions where sub-300 and nonflammability are both valuable.

Technical review updated: August 27, 2026
R480A at a glanceReference data
CompositionCO₂ / R1234ze(E) / R227ea = 5 / 86 / 9HFO/HFC/CO2 Blend
100-Year GWP291EPA Technology Transitions
Safety ClassA1ASHRAE classification
ODP0Ozone depletion potential
Phase BehaviorBlendBubble/dew data may matter
2026 RoleLower-GWPApplication-specific
Current EPA Technology Transitions GWP: 291; notable because it remains A1 and low enough for some transition pathways. GWP references from older scientific assessment bases can differ; use the value required by the applicable rule.

What is R480A refrigerant?

R480A sits in a useful middle ground. It is much lower in GWP than R134a while avoiding A2L flammability. That is why it appears in retrofit-oriented discussions and why EPA determinations have expanded its relevance in some end uses, including selected retrofit categories and certain new-equipment categories. It is not a universal answer, but it is one of the more practical A1 low-GWP profiles worth covering.

A1Safety classification of the finished refrigerant.
GWP 291Current U.S. EPA Technology Transitions reference.
BlendUse refrigerant-specific PT and charging procedures.
Technical Data

R480A refrigerant properties

Use these values for research and screening. For equipment design, charging and compliance, use the exact supplier PT data, SDS, OEM documentation and regulation that governs the project.

PropertyReferenceEngineering / source note
DesignationR480AASHRAE designation / RS-20
Nominal compositionCO₂ / R1234ze(E) / R227ea = 5 / 86 / 9Published retrofit procedure
Refrigerant typeBlendThree-component formulation
ODP0No ozone depletion
100-year GWP291EPA Technology Transitions
Safety classificationA1Nonflammable
Boiling point≈ −34.1°CPublished RS-20 data
Critical temperature≈107.4°CPublished RS-20 data
Temperature glide≈4.5°C in RS-20 retrofit dataUse exact PT chart
Primary roleR134a-class retrofit / transition refrigerantLow-GWP A1 niche
GWP values need a named reference basis

EPA Technology Transitions uses the values shown on this page. Older product literature may use IPCC AR4/AR5 or another assessment, so a different number is not automatically an error.

Applications

Where is R480A used?

Applications must be evaluated by system type, charge, compressor, heat exchanger, safety class and current regulation. The examples below describe recognized use contexts, not automatic approval for every installation.

Existing R134a systems

Often positioned as a lower-GWP retrofit option where A1 is preferred.

Water coolers

EPA determinations have expanded R480A relevance in this category.

Positive-displacement chillers

Notable because EPA added retrofit relevance here in recent determinations.

Refrigerated transport and selected refrigeration categories

Useful when a nonflammable, lower-GWP option is needed.

Commercial retrofit strategy

Evaluated where a full A2L redesign is not desired.

Legacy asset management

Can be part of extend-vs-replace decision making for R134a-based assets.

Continue through the Refrigerant Replacements and Low-GWP Refrigerants hubs for broader selection context.

Engineering Deep Dive

Why R480A attracts attention even though it is not a huge market refrigerant

Many lower-GWP refrigerants reduce GWP by moving from A1 to A2L. R480A is interesting because it reduces GWP substantially while staying A1.

That makes it appealing for owners of existing R134a-class systems who want a lower-GWP path without introducing lower-flammability system redesign.

This A1 + lower-GWP combination is the core reason R480A deserves a place in a high-quality refrigerant database.

Engineering Deep Dive

R480A is not simply 'a little better R134a'

R480A was designed around retrofit practicality, but it is still its own refrigerant with its own PT behavior, blend composition and service expectations.

Its approximate 4.5°C glide means technicians should not handle it as if it were a pure refrigerant. Correct charging, identification and performance verification remain important.

Like any retrofit, oil, seals, capacity and control behavior should be checked in the actual system.

Engineering Deep Dive

Why 9% R227ea is important

R1234ze(E) provides most of the refrigerant mass and much of the low-GWP platform, while the small CO₂ and R227ea fractions help tune the finished blend’s performance and nonflammability characteristics.

Although R227ea has a high individual GWP, its low fraction keeps the finished blend’s GWP much lower than R134a.

This is a good example of why refrigerant selection should focus on the finished blend, not only the identity of one component.

Engineering Deep Dive

Recent EPA retrofit relevance makes R480A more valuable for practical content

R480A became much more interesting when EPA expanded acceptable retrofit uses in selected categories such as cold storage, commercial ice machines, water coolers and some transport/chiller contexts.

That means R480A is not only a chemistry footnote. It can appear in real conversations about installed equipment management.

For SEO and GEO, that makes it a better topic than many refrigerants that have no clear transition story.

Key Comparison

R480A vs R513A

The table highlights engineering differences rather than implying direct interchangeability.

CharacteristicR480AR513A
EPA GWP291630
Safety classA1A1
Primary roleLow-GWP retrofit / transition optionR134a-class A1 transition blend
Sub-300YesNo
Flammability strategyNonflammableNonflammable
GlideModerateNegligible
Key appealA1 + lower GWP + retrofit storyBroad A1 familiarity
Safety & Handling

R480A safety: A1 simplifies flammability concerns, but blend practice still matters

R480A is A1, so its risk profile differs from A2L blends. However, it is still a refrigerant blend with pressure, cold-burn and asphyxiation hazards. Correct recovery, charging and identification remain important, particularly when retrofitting legacy equipment.

A1 classification

No lower-flammability system controls are required solely because of refrigerant flammability.

Blend servicing

Use correct PT data and charging procedure.

Retrofit diligence

Validate system suitability rather than assuming any R134a asset will behave identically.

Safety class is only the first layer

Actual risk depends on charge, release rate, pressure, room volume, ventilation, ignition sources, equipment construction, alarm logic and service condition.

See the Refrigerant Safety Guide for classification context.

Leak Detection

R480A refrigerant leak detection

Validate detector response to the finished blend

Leak detection for R480A should be validated for the finished blend. Depending on the application, infrared refrigerant detection may be appropriate for machinery spaces or concentration monitoring, while portable electronic leak detectors are more suitable for service diagnostics. GasNose provides a broader refrigerant gas detection entry point even where a dedicated R480A page is not available.

Portable service leak detectors, fixed area monitors, A2L mitigation sensors and refrigerant identifiers perform different functions. Define the alarm action and concentration range before selecting the technology.

2026 Regulatory Context

Regulatory position of R480A in 2026

United States

EPA Technology Transitions lists R480A at GWP 291. Recent SNAP determinations expanded R480A relevance in selected retrofit categories, including some cold-storage, commercial ice machine, chiller, refrigerated transport and water-cooler applications. End-use-specific SNAP listings should always be checked before treating it as acceptable in a given project.

European Union

R480A is well below older high-GWP HFCs but still above 150. In the EU, it can be useful as a transition refrigerant where A1 matters, but it does not carry the same long-term numerical advantage as sub-150 solutions.

Is R480A being phased out?

R480A is better described as a practical low-GWP A1 transition / retrofit refrigerant than as a fully future-proof endpoint. Its strongest value is helping owners bridge from R134a-class systems while keeping A1 safety.

Check the exact subsector and date

U.S. refrigeration limits differ by cold storage, supermarket, remote condensing, stand-alone product, industrial process and chiller category. A refrigerant may fit one pathway and fail another.

Use the Refrigerant Regulations Hub for regional research.

Alternatives & Selection

What should be compared with R480A?

Compare the real equipment pathway: retrofit vs new system, A1 vs A2L capability, GWP threshold, glide, compressor envelope, energy efficiency and service ecosystem.

Common Misconceptions

Practical misconceptions about R480A

“R480A is just R134a with a new name.”

It is a distinct three-component blend with different PT behavior and much lower GWP.

“A1 means it behaves like a pure refrigerant.”

R480A is a blend and has measurable glide.

“R480A is automatically approved for all R134a systems.”

Always check the exact EPA end use and actual equipment suitability.

“Because it contains R227ea, it cannot be low GWP.”

The finished blend is EPA GWP 291 because the high-GWP component fraction is small.

Frequently Asked Questions

R480A refrigerant FAQ

Concise answers to common composition, retrofit, glide, safety and regulation questions.

What is R480A?
R480A is a nonflammable blend used as a lower-GWP R134a-class refrigerant.
What is the composition of R480A?
Published RS-20 data show 5% CO2, 86% HFO-1234ze and 9% HFC-227ea.
What is the EPA GWP of R480A?
291.
Is R480A flammable?
No. It is classified A1.
Is R480A a retrofit refrigerant?
It is often discussed as a retrofit / transition option for selected R134a-class systems.
Does R480A have glide?
Yes, published retrofit data show measurable glide.
Why is R480A interesting?
Because it combines lower GWP with A1 safety.
Is R480A below 300 GWP?
Yes.
Can R480A replace every R134a system?
No. Retrofit suitability and SNAP end-use status must be checked.
How should R480A leaks be detected?
Use leak detection validated for the finished blend and the intended monitoring function.

Working with R480A or planning a refrigerant transition?

Compare GWP, safety class, temperature glide, equipment compatibility and regulatory lifetime before selecting a refrigerant.

Technical Notice: This page is for refrigerant research and general technical reference. Refrigerant suitability, permitted charge, equipment approval, leak mitigation, servicing procedures and regulatory compliance depend on the exact equipment, installation and jurisdiction. Always verify current manufacturer documentation, SDS, applicable standards and local regulations before selecting, replacing, charging or servicing a refrigerant.